Adjusting Sensitivity

This manual refers to the values that select ON/OFF output of the sensor amplifiers as
"Set values." In addition, the manual refers to the adjustment of set values as "Adjusting
Sensitivity." This section describes the sensitivity adjusting method.

Sensitivity adjusting method for the FS-N10 Series is broadly divided into two categories:

Preset

Simple operation allows sensitivity adjustment concurrently with correction of the
received light intensity to "

100.0

" or "

0.0

"

This function helps preventive maintenance by eliminating dispersion of the received
light intensity due to the contents of detection or individual workpieces.
However, this is not suitable for detection of transparent workpiece because there is a
small difference in the received light intensity between presence and absence of a
workpiece.

Calibration

Sensitivity can be adjusted by a simple operation. This function does not correct the
received light intensity.
This function is applied for using the received light intensity without correction or for
high-precision detection.
Calibration is also available in a preset state.

How to select sensitivity adjusting method

List of Sensitivity Adjusting Methods

Sensitivity

adjusting

method

Status of use

Functions

Contents

Reference

Preset

Basics

Using thrubeam/retro-reflective
models

Preset

When there is no workpiece, by sim-
ply pressing the PRESET button,
sensitivity adjustment is completed.

3-6

Using reflective model

Preset to maxi-
mum sensitivity

When there is no workpiece, by sim-
ply holding the PRESET button,
sensitivity adjustment is completed.

3-8

At times
like this

Not successfully displaying the
intensity level as "

100.0

" and

"

.0

" depending on the presence

of a workpiece.

Work preset

The status in which "

100.0

" or "

.0

" is

displayed can be set at your choice

3-7

Mobile object moves fast

Full automatic
preset

Preset is enabled by using a fast-
moving workpiece.

3-9

Calibration

Basic

Using thrubeam/retro-reflective
models

Two-point
calibration

The setting can be established just
by pressing the [SET] button once
when a workpiece is present and
absent.

3-11

At times
like this

Mobile body moves fast

Full automatic
calibration

Calibration is enabled by using a
fast-moving workpiece.

3-13

Using the unit in the environ-
ment that tends to get dirty
easily.

Maximum sensi-
tivity calibration

The setting seldom causes malfunc-
tion even in the environment that
tends to get dirty easily.

3-12

Using the unit for positioning

Positioning cali-
bration

The setting suitable for positioning is
available.

3-14

Using the unit for high-preci-
sion detection

Percentage cali-
bration

Effective for making correction from
external devices such as PLC.

3-15