5

Service Manual - NeoTherm 500

Control Unit is in “Standby” Mode

In certain situations, the controller on this unit can go into “Standby”

mode. The Boiler pump is running, so the unit sees a “Call for heat.”

There is no lockout or hold, but something is preventing it from going to

“Run” mode.

A4

No

Check for:

- Call for heat?

- System is up to set-point temp. - no need

for more heat?

- If warm weather shutdown is enabled:

Outdoor air temperature too warm?

Normal

operating

condition?

In certain situations, the controller on this unit can go into

“Standby” mode. The Boiler pump is running, so the unit sees a

“Call for heat.” There is no lockout or hold, but something is

preventing it from going to “Run” mode.

No

Unit operates

normally?

Disconnect outdoor temp. sensor

Yes

See Section B33

“Troubleshooting Outdoor Reset”

No

Unit operates

normally?

Set Anti-Short-Cycle to minimum value (white display = 0, current display = 1 min.)

Yes

Correct settings for Anti-Short-Cycle