B36 - ignitor assembly, Ignitor assembly – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 65

Advertising
background image

55

Service Manual - NeoTherm 500

The ignitor assembly is a two-rod system that con-

sists of a ground rod and a spark rod.

Adjustment Procedure:
1. Shut off the 120V power supply to the unit.
2. Turn off all manual gas valves connecting the unit

to the main gas supply line.

3. Remove the front door of the unit to gain access

to the ignitor assembly.

4. The end of each spark rod should be 1/4” away

from the burner.

5. Set the gap between the spark rods at 3/16” ±

1/16.”

Replacement Procedure:
1. Shut off the 120V power supply to the unit.
2. Turn off all manual gas valves connecting the unit

to the main gas supply line.

3. Remove the front door of the unit to gain access

to the ignitor assembly.

4. Remove the two wires connected to the assem-

bly.

5. Remove the two bolts connecting the ignitor

assembly to the burner door. Remove the old

ignitor assembly.

6. Install a new assembly by reversing the instruc-

tions listed above. Replace the ignitor assembly

gasket if it is damaged.

Fig. B36-1 - Spark rods and flame sensor

Flame sensor

Spark rods

Fig. B36-2 - Correct setting for spark gap

Flame sensor:

1/4” clearance

to burner

Spark rods:

1/4” clearance

to burner

Gap between

spark rods:

3/16” ± 1/16”

B36

Ignitor Assembly

Advertising
This manual is related to the following products: