B19 - checking the air pressure switch, Checking the air pressure switch, Blower proving switch – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 48: See section b19, Checking the air, Pressure switch, If the pressure switch remains open, go to sec, Tion b19, “checking the air pressure switch, See procedure b19

Advertising
background image

38

Service Manual - NeoTherm 500

Exhaust vent

blocked?

Yes

No

Clear the vents.

Check the bird screens

or terminals.

Check for blocked air intake

and exhaust vents.

Clean with a shop-vac.

Dirty fan?

Yes

No

Test the air pressure switch.

(See Section B20.)

Switch is OK?

No

Replace switch.

Yes

Problem with

blower?

Yes

See Section B22 -

“Checking the Blower”

No

Heat exchanger

is plugged?

Yes

Clean the heat

exchanger.

See Section C5.

B19

Checking the Air Pressure Switch - Blower Proving Switch

Advertising
This manual is related to the following products: