29

Service Manual - NeoTherm 500

Checking the High Gas Pressure Switch

B12

The high gas pressure switch is a 24V manual reset switch that acts to

cut power to the gas valve if the gas pressure is too high for proper op-

eration. The type of switch used is integrally vent limited, and does not

require venting to the atmosphere.

24V AC present?

(switch open)

Yes

Check gas supply.

Call gas company.

Gas pressure should be

lower than 13” w.c.

Check for 24V AC across

the switch.

Reset the switch manually

by pressing the button.

WARNING -

Never jump this

switch!

Switch resets?

No

Yes

Temporary drop in

gas pressure.

Switch is OK.

Gas supply OK?

No

Call the gas company

and correct the problem.

(If the switch was tripped, you will feel a resistance.

The voltage should return at the switch terminals.)

Yes

Replace if necessary.

See Section B15.

Advertising
This manual is related to the following products: