Service Manual - NeoTherm 500

Testing the Low Gas Pressure Switch

B14

In the gas train, this switch is located before the gas

control valve. Gas will reach this switch whenever the

gas shutoff valve to the unit is open.
Figure B14-1 shows the gas train. Connect a test gauge

to the inlet gas pressure tap.
The low pressure switch (Honeywell p/n C6097A) is

wired N.O. (normally open), and requires a manual re-

set. (You will need to reset this switch if you disconnect

an old switch or install a new switch.) The low pressure

switch is set to trip below 3” W.C. (water column).

Fig. B14-1 - Inlet gas pressure tap

Inlet gas

pressure

tap