B20 - test procedure for air pressure switch, Test procedure for air pressure switch, Removing and replacing the air pressure switch – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 49: Test the air pressure switch, See section b20.)

Advertising
background image

39

Service Manual - NeoTherm 500

1. The switch is located behind the front panel. Dis-

connect the two leads, and connect a Volt-Ohmme-

ter set to check for continuity (reading Ohms).

2. Insert a hose “T” in the clear plastic hose that runs

to the positive pressure port (closest to the electrical

connections). Attach a length of hose to the branch

of the “T.”

3. Blow on the end of the hose.

With pressure –

You should see continuity (low Ohms - switch

closed)

Without pressure –

You should not see continuity (high Ohms – switch

open)

4. Disconnect the “T.” Attach a manometer to the

negative port on the blower. When the fan starts,

you should see a vacuum of about ½” w.c.

Removing and Replacing the Air Pressure Switch

Fig. B21-1 - Air pressure switch (typical)

The air pressure switch acts as a “blower proving switch”

to ensure that the blower is running before the unit will

fire.
Tools and equipment required
• Small Phillips-head screwdriver (#1) or 5/16” socket
• Small standard pliers
• Electrical tape

B20

Test Procedure for Air Pressure Switch

B21

Advertising
This manual is related to the following products: