B9 - testing the flow switch, Testing the flow switch – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 33

Advertising
background image

23

Service Manual - NeoTherm 500

Testing the Flow Switch

The flow switch uses a set of paddles to sense water

flowing through the system. See Fig. B9-2. When

water is flowing, the switch is normally closed (N.C.).

If the water flow stops, the switch opens. After a “no

flow” condition, the switch resets itself immediately

and automatically.
Shut off power to the boiler, and remove the cover on

the switch. Use a volt-ohmmeter to test the continu-

ity through the switch. With no water flow and the

paddles in the “relaxed” position (standing upright),

the switch should be open.
Note - There is a seal at the base of the paddle as-

sembly. If this seal fails, it can allow water to leak

into the connection box. From there, the water can

flow through conduits to other parts of the control

system in the Magna-Therm unit.
If it is necessary to replace the flow switch, see Sec-

tion B10 for instructions.

Fig. B9-1 – Typical flow switch installation

B9

Fig. B9-3 – Flow switch with cover removed

Fig. B9-2 - Metal paddles used to detect water flow

(typical)

Advertising
This manual is related to the following products: