Service Manual - NeoTherm 500

Unit is Running, But Building is Still Cold

A6

Yes

No

Clear it

Air inlet is

blocked?

Clean

Air intake

inside unit is

plugged?

Yes

No

Clean, blow out

(Gas/air mixture is correct,

but not enough gas/air

mixture is supplied.)

Dirty fan?

Yes

No

Burner and/or

heat exchanger

plugged?

Yes

See “Cleaning the Burner and Heat Exchanger”

Section C5