C4 - troubleshooting combustion problems, Troubleshooting combustion problems – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 74

Advertising
background image

64

Service Manual - NeoTherm 500

Troubleshooting Combustion Problems

During adjiustment,

can reach target

figures in Table?

Cannot reach

Gas inlet

pressure OK?

Yes

No

Gas supply problem.

Check with gas company.

Interior of burner

is clean?

No

Clean burner and heat exchanger.

See Section C5.

Can reach

Combustion

is OK.

Replace gas valve.

Any gas leaks

inside the unit?

No

Check all hoses,

tighten all connections.

Yes

C4