Combustion adjustment procedure, Units with original (white) user interface – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 70

Advertising
background image

60

Service Manual - NeoTherm 500

Combustion Adjustment Procedure -

Units with Original (White) User Interface

WARNING

Improper adjustment may lead to poor combustion quality, increasing

the amount of carbon monoxide produced. Excessive carbon monox-

ide levels may lead to personal injury or death.


Equipment required:
• Combustion analyzer
• 2 mm Allen wrench

Procedure:
1. Measure the CO

2

and O

2

in the flue products at High

Fire. The NeoTherm must be forced to High Fire to

obtain accurate results.

How to get there: From the “Home” screen, press

and hold the Next button for 3 seconds to go to

Diagnostic mode. Press the Next button several

times until you see “Rate” and “100%.” Press the Up

arrow. The NT unit is now forced into high fire for 5

minutes.

The CO

2

readings should be between the values

shown in Table C2-1. If the CO

2

is not within the

range shown, adjustments may be made. To adjust

the high fire CO

2

, locate the high fire adjuster screw

as shown in Fig. C2-1. Slowly make adjustments in

1/16 of a revolution increments until the CO

2

is within

the range identified. For the high fire adjustment,

turning the screw counter-clockwise (CCW) makes

the mixture richer.

Low fire CO

2

adjustment

High fire CO

2

adjustment

Fig. C2-1 - High- and low-fire adjustments on gas valve

Gas Type

High Fire CO

2

Low Fire CO

2

Natural

8.8% to 9.0%

0.5% lower than high fire CO

2

Propane

9.8% to 10.0%

0.5% lower than high fire CO

2

Table C2-1 - CO

2

Range

C2

Advertising
This manual is related to the following products: