B30 - outlet water temperature sensor, Outlet water temperature sensor, Removing and replacing the – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 60

Advertising
background image

50

Service Manual - NeoTherm 500

Fig. B30-1 - Outlet water temperature sensor (typical)

The outlet water temperature switch allows the control

system to monitor the temperature of the water as it

leaves the NT unit. A typical installation for the outlet

water temperature sensor is shown in Fig. B30-1. The

sensor is connected to J8 8-9-10 on the control module.
This sensor assembly includes two electronic devices

called “thermistors.” As long as the resistance readings

from both sensors agree, the Magna-Therm will continue

to operate. If there is a large difference between the

readings, or if one of the thermistors is “open” or “short-

ed,” the control system will shut down the NT unit and

display a “Hold 92” error message.
For instructions on testing the assembly, see Section

B32.
To reset the control system after the outlet sensor trips:
• On a unit with the original (white) user interface -

Press the Reset button near the lower left-hand

corner of the display. This will reset the lockout, and

the lockout code will disappear.

• On a unit with current user interface -

Reset by pressing the OK button.

Removing and Replacing the Outlet Water Temperature Sensor

See Fig. B30-1 for a typical installation.

Tools and equipment required:
• Crescent wrench or 14 mm socket
• Pipe dope or Teflon® tape

Procedure:
1. Turn off power to the system. Use the main disconnect switch mounted above

the front panel.

2. Isolate the boiler. Turn off the water shutoff valves located upstream and down-

stream of the unit.

3. Drain the boiler. The drain valve is located near the lower end of the heat ex-

changer.

Sensor

Water outlet

pipe

B30

Outlet Water Temperature Sensor

B31

Advertising
This manual is related to the following products: