B13 - checking the low gas pressure switch, Checking the low gas pressure switch, Section b13 - low gas pressure switch – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 40

Advertising
background image

30

Service Manual - NeoTherm 500

Checking the Low Gas Pressure Switch

The low gas pressure switch is a 24V manual reset switch that acts to cut

power to the gas valve if the gas pressure is too low for proper operation.

The type of switch used is integrally vent limited, and does not require

venting to the atmosphere.

24V AC present?

(switch open)

Yes

Check gas supply.

Call gas company.

Gas pressure should be

greater than 3” w.c.

Check for 24V AC across

the switch.

Reset the switch manually

by pressing the button.

WARNING -

Never jump this

switch!

Switch resets?

No

Yes

Temporary drop in

gas pressure.

Switch is OK.

Gas supply OK?

No

Call the gas company

and correct the problem.

(If the switch was tripped, you will feel a resistance.

The voltage should return at the switch terminals.)

Yes

Test the switch. See Section B14

Replace if necessary.

See Section B15

B13

Advertising