B24 - high stack temperature fault, High stack temperature fault – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 56

Advertising
background image

46

Service Manual - NeoTherm 500

Yes

No

Correct this immediately.

Blocked exhaust outlet?

Dirty heat exchanger?

If you have the current user interface,

set the stack temperature limit to 190°F.

Actual stack

temperature

problem?

Check the continuity on the wires from

the sensor to J9-4, J9-5, and J9-6 on the

control module.

Wiring to

sensor is correct? Good

connections?

No

Yes

Fault disappears?

No

Replace the control module.

Replace the sensor.

See Section B38.

Problem

with circulator

pump?

Yes

No

B24

High Stack Temperature Fault