B24 - high stack temperature fault, High stack temperature fault – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual
Page 56
Advertising
46
Service Manual - NeoTherm 500
Yes
No
Correct this immediately.
Blocked exhaust outlet?
Dirty heat exchanger?
If you have the current user interface,
set the stack temperature limit to 190°F.
Actual stack
temperature
problem?
Check the continuity on the wires from
the sensor to J9-4, J9-5, and J9-6 on the
control module.
Wiring to
sensor is correct? Good
connections?
No
Yes
Fault disappears?
No
Replace the control module.
Replace the sensor.
Problem
with circulator
pump?
Yes
No
B24
High Stack Temperature Fault