Checking the Condensate Trap Level Switch

24V AC present?

(switch open)

No

Yes

See Section B3 -

“Checking the Safety Chain”

Check for 24V AC across switch.

Test switch. See Section B17.

Replace if necessary.

See Section B18.

Outlet blocked?

No

Yes

Flush outlet with water.

Check for blocked or frozen condensate outlet.