B38 - pump fault, Pump fault – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 67

Advertising
background image

57

Service Manual - NeoTherm 500

A problem with the circulator pump could appear as

a #79 error (Outlet High Limit). It could also appear

as a #63 error (LCI - Limit Control Input) if the safety

chain includes a flow switch. The SOLA controller

also can display error #51 - Pump Fault.

No

No

Check for 120V at terminals

1 and 2 on TB5.

Pump is

getting power?

Disassemble and/or replace pump

Pump sounds

different?

No

Yes

Pump is

moving water?

No

Replace pump

Pump is

running?

Yes

Yes

Disassemble and/or replace pump

B38

Pump Fault