A8 - open safety chain - fault #63, Control unit says “run”, but boiler is not firing, Open safety chain - fault #63 – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 19: Control unit says “run” but boiler is not firing, A7 a8, Control unit says “run,” but boiler is not firing

Advertising
background image

9

Service Manual - NeoTherm 500

Control Unit Says “Run,” But Boiler is Not Firing

In this condition, the panel is lighted, so you know the unit has power.

The Boiler pump is running, so you know the unit is receiving the call

for heat. The blower is running, the unit has spark, and the gas valve is

operating correctly.

Open Safety Chain - Fault #63

This fault indication can point to several different problems:
• Blocked condensate drain
* Blocked exhaust vent
• High or low gas pressure
• Low water in system
• Problem with circulator pump
Fault #63 is a bit like the “Check Engine” light in a car - it indicates a problem, but

does not identify the problem. To identify the specific problem, see Section B3 -

“Checking the Safety Interlocks.”

A7

A8

No

Example:

Stack temp. limit trips,

automatically resets after 20 minutes.

Until this happens, the display says

“Run” but the unit will not fire.

Unit is operating

correctly - recovering

from a trouble

condition?

No

Check safety

interlocks

(Sect. B3)

OK?

Replace the SOLA controller

See Section D8, D9

Advertising
This manual is related to the following products: