B1 - quick check of components in the safety chain, Quick check of components in the, Safety chain – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual

Page 21: See “quick check of components, In the safety chain and, Firing sequence” - section b1, Quick check of components in the safety chain, Fig. b1-2 - simulating a “call for heat” input, Tb7 1-2, Tb7 5-6

Advertising
background image

11

Service Manual - NeoTherm 500

Quick Check of Components in the Safety Chain

This procedure gives you a quick way of checking the safety switches

and some of the control functions in the unit. This will allow you to rule

out some large sections of the control system, and find the part of the

system that actually has the problem.
DANGER! - When the cover is opened, some of the areas carrying 120V

AC voltage will not be covered. Do not perform the following tests unless

you have been trained how to do this safely by Laars.

FIELD

INTER-

LOCK

REMOTE

ANALOG

INPUT

OUTDOOR

TEMP

SENSOR

BOILER

PUMP

SYSTEM

PUMP

DHW

PUMP

H2309800E

ATTACH

GROUND

WIRE HERE
ATTACHEZ

LE FIL DE

TERRE LCI

1. Remove the front panel assembly and front bezel.
2. Before you start troubleshooting, you should

disconnect some parts of the system to make

the troubleshooting simpler. If a sensor for the

Outdoor Reset function is connected, disconnect

it at terminals 1 and 2 on TB-7 on the control

board. See Fig. B1-1. (Remember to re-connect

the sensor when you are done.)

If the unit operates with the Outdoor Reset sen-

sor disconnected, go to Section B33 - “Trouble-

shooting the Outdoor Reset System.”

3. Turn off the Anti Short Cycle function by setting it

to the minimum value.

4. If you are working with a boiler which can pro-

duce both hydronic heat and domestic hot water,

work with just one function at a time. This will

make it clear whether the “call for heat” is coming

from the hydronic side of the system or the DHW

side.

5. Insert a jumper across terminals 5 and 6 on TB-7

on the control board. See Fig. B1-2. This will

create a permanent “call for heat” signal. (Again,

remember to remove this when you are through.)

Fig. B1-1 - Terminals for outdoor reset

TB7 1-2

FIELD

INTER-

LOCK

REMOTE

ANALOG

INPUT

OUTDOOR

TEMP

SENSOR

BOILER

PUMP

SYSTEM

PUMP

DHW

PUMP

H2309800E

ATTACH

GROUND

WIRE HERE
ATTACHEZ

LE FIL DE

TERRE LCI

Fig. B1-2 - Simulating a “call for heat” input

TB7 5-6

B1

Advertising
This manual is related to the following products: