6.3. 24 V DC Power Supply Expansion

If the addition of zones causes the total of current consumption of 24 V DC-operated equipment to exceed 5
A, then add the required number of the FS-7000PS panels.

[Notes]
• Make connections between negative (–) terminals of the 24VDC output of all FS-7000PS panels.
• Divide the power supply to 24 V DC-operated equipment in order to keep the current supplied from a single

FS-7000PS panel at 5A or less. (Refer to the following table showing each component's current
consumption at 24 V DC.)

Current Consumption

200 mA

150 mA

450 mA

200 mA

130 mA

Equipment

FS-7000CP

FS-7010CP

FS-7000JP

FS-7000AT

FS-7000EV

Current Consumption

110 mA

60 mA

90 mA

15 mA

Equipment

FS-7000GM

FS-7000RF

FS-7000RM

FS-7010RM

[Wiring Diagram]
The following figure shows only the wiring related to the expansion of the 24 V DC power supply.

230 V AC

FS-7000PS

230 V AC

FS-7000PS

DC POWER OUT

DC POWER OUT

To 24 V DC input of each DC-operated component

Cables used:

(See page 66; Table for Cables.)