Toa FS-7000 SERIES Installation User Manual

Page 61

Advertising
background image

61

Storage battery capacity C (Ah) =

[ K

1

I

1

+ K

2

( I

2

- I

1

) ]

Where,
C: Required storage battery capacity at 25°C
L: Maintenance rate* (generally 0.8)
K

1

: Capacity conversion time corresponding to the sum (T

1

+T

2

) of Waiting time T

1

and Operation time T

2

.

K

2

: Capacity conversion time corresponding to Operation time T

2

.

I

1

: Current consumption in standby mode from the time that power fails until emergency broadcasting begins.

This is the sum of all currents needed by the FS-7000EV, DS-029B, and other equipment consuming
power even during power failures.

I

2

: Power consumption during emergency broadcasts (the 24 V DC current consumption of the entire

system). When 4-wire system attenuators are connected, their current consumptions are also included.

*Maintenance rate is a correction value used to guarantee needed battery capacity and satisfy specified load

characteristics while accounting for variations caused by battery age and usage conditions. As a general
guideline, it is assumed that battery capacity decreased to 80% of the original represents the end of the
battery's useful life, and therefore a maintenance rate of 0.8 is used in these calculations.

Table 1. Battery Capacity Conversion Time Table

1

L

Capacity Conversion Time K (hours)

0.333

0.575

0.820

1.06

1.30

1.55

1.80

2.05

2.28

2.50

Discharge Time (minutes)

10

20

30

40

50

60

70

80

90

100

Current Consumption (A)

Operation

0.20

0.15

0.45

0.20

0.13

0.11

Model No.

FS-7000CP

FS-7010CP

FS-7000JP

FS-7000AT

FS-7000EV

FS-7000GM

Standby

0.00

0.00

0.00

0.00

0.01

0.00

Current Consumption (A)

Operation

0.06

0.09

0.015

0.07

0.05

Model No.

FS-7000RF

FS-7000RM

FS-7010RM

FS-7000PS

DS-029B

Standby

0.00

0.00

0.00

0.00

0.03

Confirm attenuator current consumption using the relevant specification sheets or manuals.

When capacity conversion coefficients corresponding to the operation time (discharge time) of more than 100
minutes is needed, approximate values can be obtained from the following expression:

Capacity conversion time K = 0.0217 x Discharge time + 0.33 ......... (A)

Table 2. Current Consumption During Power Failures