[Calculation Example]

Storage battery capacity required for a system of the following configuration to operate for 10 minutes after
waiting for an hour from the start of a power failure can be calculated as follows:

System Configuration

Current Consumption (A)

Operation Mode

0.20

0.45

0.13

0.07

0.05

0.90

Model No.

FS-7000CP

FS-7000JP

FS-7000EV

FS-7000PS

DS-029B

Total

Quantity

1

1

1

1

1

-

Standby Mode

0.00

0.00

0.01

0.00

0.03

0.04

K

1

: 1.80 (60 minutes of standby time + 10 minutes of operation time = 70-minute capacity conversion time)

K

2

: 0.333 (capacity conversion time for 10-minute operation time)

I

1

: 0.04 A (total standby current consumption from the above table)

I

2

: 0.90 A (total operation current consumption from the above table)

Battery capacity C (Ah) =

[ 1.8 x I

1

+ 0.333 ( I

2

- I

1

) ]

=

[ 1.8 x 0.04 +0.333 ( 0.90 - 0.04 ) ]

= 0.45

From this, it can be seen that if a battery with capacity of 0.45 Ah is used, the system will be able to operate
for 10 minutes.