Initialisation of administration data blocks, Sb070 init_mbs, Sb071 init_mbs – Pilz PSS SB NOT, Basic license User Manual

Page 46: Standard function blocks

Advertising
background image

6-4

Standard Function Blocks

Modular Block System: Emergency Stop Circuits

Initialisation of administration data blocks

SB070

INIT_MBS

SB070 exclusively initialises administration data block DB015 with global
parameters. For this reason it can only be used in applications which:

• Comprise a maximum of 200 standard function blocks

• Do not use standard function blocks SB063, SB064 and SB065

SB071

INIT_MBS

SB071 initialises all three administration data blocks (DB015, DB016 and
DB017) with global parameters. It can be used for all applications.

NOTICE
SB071 is essential if you are using any one of the following standard
function blocks:

• SB063

• SB064

• SB065

In this case, the use of SB071 is firmly specified.

Advertising