Modular Block System: Emergency Stop Circuits

Standard Function Blocks

- Bit 06:

Faults which occur as the pulse edge changes at the input
parameter

EIN

Faults which occur as the pulse edge changes at the inputRFK
2 interrupted
Remedy: Check contacts, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 07:

Faults which occur as the pulse edge changes at the input
parameter

EIN

RFK 2 closed
Remedy: Check contacts, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 08:

Faults which occur as the pulse edge changes at the input
parameter

EIN

Reset input constantly high or set too early
Remedy: Release reset button and press it again. If this does
not work, check contacts, cable, input card and all conditions
and then reset (input parameter

RSET)

• Error messages on the CPU-display

- None

Global parameters used in administration data block DB015

Global parameters may be set in OB120 using SB070.

• DW1002: Number of cycles for reaction time of RFK

Blocks required

• DB015:

Administration data block

DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.

• SB070

Initialisation of global parameters in DB015

SB067