6-18

Modular Block System: Emergency Stop Circuits

Standard Function Blocks

SB063

SB063: Emergency stop monitoring, category 4

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 600
Format: Word constants KF000001 ... KF000600
(see sections in Chapter 5 entitled “Administration data blocks
DB015, DB016 and DB017” and “Input parameter SSNR”).

GRP:

I/O-Group status flag (SafetyBUS p) containing the inputs
NC_1 and NC_2 (M116.00 for I/O-Group 0 to M116.31 for
I/O-Group 31)
If the SB is being used without SafetyBUS p, the input
parameter must be assigned RLO-1.

NC_1:

E-STOP N/C contact 1

NC_2:

E-STOP N/C contact 2

AuSt:

Reset on start-up (PSS cold start) or when I/O-Group is started
(SafetyBUS p)
AuSt = 0: Initial reset required.
Sequence: When the PSS is cold/warm started or the I/O-
Group is started (

GRP = 0/1-pulse edge), an initial reset is

required through input parameter

RSET, in order to trigger the

enable.

SB063

E-STOP

W - SSNR
X - GRP
X - NC_1
X - NC_2
X - AuSt
X - ARSt
X - FTST
X - RSET

ENBL - X