Standard function blocks, Sb061 – Pilz PSS SB NOT, Basic license User Manual

Page 54

Advertising
background image

6-12

Modular Block System: Emergency Stop Circuits

Standard Function Blocks

- Bit 03:

With: “Automatic reset (PSS cold start)”:
E-STOP button operated and reset button pressed
Remedy: Check button, cable and input card, release E-STOP
button and reset again (input parameter

EIN).

With: “Automatic reset when E-STOP button is released”:
E-STOP button operated
Remedy: Release E-STOP button

- Bit 08:

E-STOP released, ready for reset
Remedy: Press reset button (input parameter

EIN)

- Bit 09:

Reset button pressed constantly (i.e. stuck in)
Remedy: Check button, cable and input card, release E-STOP
button and reset again (input parameter

EIN)

- Bit 10:

Reset successful, but N/C contact S1_Ö failed to open when
the E-STOP button was operated.
Remedy: Press E-STOP button again to ensure that contacts
open correctly and then reset; otherwise: check cable and
input card, release the E-STOP button and reset (input
parameter

EIN)

- Bit 11:

Reset successful, but N/C contact S2_Ö failed to open when
the E-STOP button was operated.
Remedy: Press E-STOP button again to ensure that contacts
open correctly and then reset; otherwise: check cable and
input card, release the E-STOP button and reset (input
parameter

EIN)

• Error messages on the CPU-display

- E 001:

Parameter error
SSNR does not lie within the limits of 1 ... 200

SB061