Examples – Pilz PSS SB NOT, Basic license User Manual

Page 94

Advertising
background image

8-10

Examples

Modular Block System: Emergency Stop Circuits

Feedback loop monitoring (shutdown with two contactors connected in
series), category 4

Block used: SB065/FBL

INFORMATION
To achieve category 4, two independent shutdown routes must be
available within the current path of the potentially dangerous drive. This
can be achieved, for example, by connecting two contactors in series.

Please note:
The feedback loops must be wired inside the control cabinet.

Fig. 8-9: Wiring diagram

L1

24 V

N

M1

M

K-M1.2

K-M1.1

FBL

K-M1.1

FBL

K-M1.2

M1

EIN

E0.01

E0.02

E0.08

PSS

A1.00

K-M1.1

K-M1.2

A1.08

Advertising