Output parameters, Error messages – Pilz PSS SB NOT, Basic license User Manual

Page 53

Advertising
background image

Modular Block System: Emergency Stop Circuits

6-11

QAut = 1:

Automatic reset when

EIN = 1:

E-STOP-button is released

QAnf = 0:

INFORMATION
Automatic reset is only possible in conjunction with:
EIN = RLO-1 (M 110.01) and
QAnf = RLO-0 (M 110.00).
This means that an automatic reset
(

QAut = 1) and a reset on PSS start-up

(

QAnf = 1) are mutually exclusive.

Output parameters

FG:

Enable flag bit
FG = 0:

Not enabled

FG = 1:

Function enabled when no errors are present

Error messages

Any fault that is detected will be stored in the corresponding error data
word (

SSNR) of DB 015 (1st data block), until the fault has been fully dealt

with.

• Error messages in DB 015

- Bit 00:

E-STOP button operated
Remedy: Check button, cable and input card, release E-STOP
button and reset (input parameter

EIN)

- Bit 01:

Contact synchronisation time exceeded for N/C contact

S1_Ö

Remedy: Check button, cable and input card, release E-STOP
button and reset (input parameter

EIN)

- Bit 02:

Contact synchronisation time exceeded for N/C contact

S2_Ö

Remedy: Check button, cable and input card, release E-STOP
button and reset (input parameter

EIN)