Examples

Modular Block System: Emergency Stop Circuits

Feedback loop monitoring (selective shutdown), category 4

Block used: SB067/RFK_K4

WARNING!

If only one contactor is used to switch a potentially dangerous drive, it
must be possible to switch this contactor off via a group contactor situated
within the current path. This group contactor must be controlled with the
AND-linked FG-signals of the individual main contactors and must be
monitored with a feedback loop.

The subordinate main contactors may only switch on if the group contactor
monitor

FG = 1. The switch-on signal from the subordinate contactors

must form an AND-connection with the FG-signal from the group contactor
and must be assigned to the

Ein-parameter of the main contactor monitor.

If only one feedback loop is used, the feedback input will be connected to
RFK1 and RFK2.

Please note:
The feedback loops must be wired inside the control cabinet. If this is not
possible, the feedback loops must be pulsed.

Fig 8-13: Wiring diagram

L1

24 V

N

M1.1

K-M1.1

K-G1

RFK
K-M1.1

E0.0

E0.1

PSS

+ A1.16 -

K-M1.1

K-M1.2

M1.2

K-M1.2

E0.8

RFK
K-G1

M1.1
START

RFK
K-M1.2

E0.2

E0.9

M1.2
START

K-G1

0 V

M

M

+ A1.17 -

+ A1.18 -