Blocks required – Pilz PSS SB NOT, Basic license User Manual

Page 63

Advertising
background image

Modular Block System: Emergency Stop Circuits

6-21

- Bit 08:

Synchronisation error N/C contact 2
Remedy: Check button, cable and input card, release the E-
STOP button and perform a function test (press E-STOP
button, release it and reset (input parameter

RSET))

- Bit 09:

I/O-Group stop triggered while PSS is in RUN mode
Remedy: Start I/O-Group

• Error messages on the CPU-display

- E003

Administration data block has not been initialised
Remedy: Call SB071 in OB120

Global parameters used in the administration data blocks

The global parameter may be set in OB120 using SB071.
• DW1001: Number of cycles in the contact synchronisation time between

the 2 N/C contacts on the E-STOP button

Blocks required

• DB015, DB016, DB017: Administration data blocks

The data blocks must consist of their total length of 1024 data
words and have READ/WRITE access (see Chapter 5, section
entitled “Administration data blocks...”).

• SB071:

Initialisation of global parameters in DB015, DB016 and DB017