Modular Block System: Emergency Stop Circuits

6-29

Error messages

Any fault that is detected will be stored in the corresponding error data
word (

SSNR) of DB015 (1st data block), until the fault has been fully dealt

with.

• Error messages in DB015

- Bit 00: Faults which occur as the pulse edge changes at the input

parameter

EIN

RFK 1 remains open
Remedy: Check contacts, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 01:

Faults which occur as the pulse edge changes at the input
parameter

EIN

RFK 1 remains closed
Remedy: Check contacts, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 02:

Faults which occur as the pulse edge changes at the input
parameter

EIN

RFK 2 remains open
Remedy: Check contacts, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 03:

Faults which occur as the pulse edge changes at the input
parameter

EIN

RFK 2 remains closed
Remedy: Check contacts, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 04:

Faults which occur as the pulse edge changes at the input
parameter

EIN

RFK 1 interrupted
Remedy: Check contacts, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 05:

Faults which occur as the pulse edge changes at the input
parameter

EIN

RFK 1 closed
Remedy: Check contacts, cable, input card and all conditions
and then reset (input parameter

RSET)