6-34

Modular Block System: Emergency Stop Circuits

Standard Function Blocks

SB070

Please note:

Entering excessively high time values for monitoring operations will reduce
the safety level of your machine.

If you are using type 2 ESPE/AOPD devices, a maximum value of 150 ms
may be entered for parameter

RBWS (EN 61 496-1).

• The number of cycles calculated is rounded down and transmitted to the

data words in administration data block DB 015.

• The SB must be called up once only when the PSS is started up

(e.g. in OB120).

Error messages

• None

Blocks required

• OB120

• DB015:

Administration data block

DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.