Examples – Pilz PSS SB NOT, Basic license User Manual

Page 96

Advertising
background image

8-12

Examples

Modular Block System: Emergency Stop Circuits

Fig 8-11: Wiring diagram

Feedback loop monitoring (shutdown with two main contactors
connected in series and pulsed outputs), category 4

Block: SB067/RFK_K4

INFORMATION
If wired outside the control cabinet, or if there is any possibility of a short
circuit, the feedback loops must be allocated pulsed outputs (A0.16 and
A0.17); this must be entered in the configurator (DB002).

L1

24 V

N

M1

K-M1.2

K-M1.1

RFK
K-M1.1

RFK
K-M1.2

M1
START

E0.01

E0.02

E0.08

PSS

+ A1.16 -

K-M1.1

K-M1.2

A0.16 A0.17

pulsed outputs

M