Modular Block System: Emergency Stop Circuits

6-7

Output parameters

FG:

Enable flag bit
FG = 0:

Not enabled

FG = 1:

Function enabled when no errors are present

Error messages

Any fault that is detected will be stored in the corresponding error data
word (

SSNR) of DB 015 (1st data block), until the fault has been fully dealt

with.

• Error messages in DB015

- Bit 09:

E-STOP button operated
Remedy: Check button, cable and input card, release E-STOP
button and reset (input parameter

EIN)

- Bit 14:

Reset button pressed constantly (i.e. stuck in)
Remedy: Check button, cable and input card, release E-STOP
button and reset again (input parameter

EIN)

- Bit 15:

E-STOP released, ready for reset.
Remedy: Press reset button (input parameter

EIN)

• Error messages on the CPU-display

- E 001:

Parameter error
SSNR does not lie within the limits of 1 ... 200

- E 002:

Parameter error
SSNR assigned more than once OR
DW1015 in DB015 was not incremented