Modular Block System: Emergency Stop Circuits

Standard Function Blocks

SB060: Emergency stop monitoring, category 2

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte constants KB001 ... KB200
(see sections in Chapter 5 entitled “Administration data blocks
DB015, DB016 and DB017” and “Input parameter SSNR”).

EIN:

Reset button (N/O contact)
EIN = 0/1-pulse edge: Reset occurs

S1_Ö :

E-STOP N/C contact

QAnf:

Automatic reset (PSS cold start)
QAnf = RLO-0 (M 110.00): No reset required.

Cycle: When the PSS is started up (PSS switched
off/on) or cold started (PSS STOP/RUN), the
enable is triggered without an additional reset.

QAnf = RLO-1 (M 110.01): Reset required.

Cycle: When the PSS is started up (PSS switched
off/on) or cold started (PSS STOP/RUN), a reset
is required through the input parameter

EIN in

order to trigger the enable.

QAut:

Automatic reset when E-STOP button is released
QAut = RLO-0 (M 110.00): Reset through input parameter EIN

is required.

QAut = RLO-1 (M 110.01): Automatic reset when E-STOP is

released. The value of input parameter

EIN is

irrelevant.

SB060

SB 060

NA_Kat_2

B - SSNR
X - EIN
X - S1_Ö
X - QAnf
X - QAut