(2) Power consumption curve

How to read the power consumption curve

< NOTE >

Water flow rate at 4.8 GPM is a reference value corresponding to various power consumption at

various entering water temperature. From reference curve, read power consumption at various

water flow rate (see example of how to read power consumption).

ILL00224-00

Power Consumption at 4.8 GPM (kW)

Power Consumption (kW)

0.8

35

(2)

45

(7)

55

(13)

65

(18)

75

(24)

85

(29)

95

(35)

2.4 3.6 4.8 6.0 7.2

0.9

1.0

1.1

1.2

1.3

1.4

1.5

0.8

0.9

1

1.1

1.2

1.3

1.4

1.5

Entering Water Temp. °F (°C)

Water Flow (GPM)

ILL00225-00

Power Consumption at 4.8 GPM (kW)

Power Consumption (kW)

0.8

35

(2)

45

(7)

55

(13)

65

(18)

75

(24)

85

(29)

95

(35)

2.4 3.6 4.8 6.0 7.2

0.9

1.0

1.1

1.2

1.3

1.4

1.5

0.8

0.9

1

1.1

1.2

1.3

1.4

1.5

Entering Water Temp. °F (°C)

Water Flow (GPM)

Example: EWT: 85 °F (29 °C), Water flow: 7.2 GPM
Power Consumption: 1.22 kW