5. WATER SYSTEM

5.1 Water Regulating Valve

• This unit is equipped with a water regulating

valve to operate within wide water temperature

range. This water regulating valve

automatically controls the water flow rate to

stabilize the refrigeration system and it has an

adjusting bolt to adjust the valve opening

temperature.

5.2 Default Water Regulating Valve Setting and Operation Range

• Default setting of the valve opening temperature is 86 °F (30 °C) and marked on the valve

housing. If the entering water temperature is below 86 °F (30 °C), there is no loss of water while

the unit is not operating. Adjustment of this valve setting is required only when the unit will be

used under the following conditions.

Entering water temperature is below 68 °F (20 °C):

Valve setting must be adjusted to lower temperature to extend the life of the compressor.

Entering water temperature is above 86 °F (30 °C):

Valve setting must be adjusted to higher temperature to prevent wasted water.

< NOTE >

This adjustment expands the minimum water temperature range. Carefully control the operating

range.

CAUTION

Failure to adjust the water regulating valve or operating the unit with entering water temperature

below 68 °F (20 °C) without adjusting the valve setting may damage the unit and void the

warranty.

ILL00186-00

Adjusting Bolt

Water Regulating Valve