3 adjustment of water regulating valve setting, Adjustment of water regulating valve setting – MovinCool Office Pro W20 Service Manual User Manual

Page 25

Advertising
background image

Operation Section

25

5.3 Adjustment of Water Regulating Valve Setting

1) Stop the unit and unplug the power cord. Then

shut off the water supply.

2) Remove five (5) screws from the service panel on

the rear side of the unit.

3) Remove thirteen (13) screws from the rear panel.

4) Check the valve setting guide table on the inside

panel of the unit to confirm the current valve

setting. If the table is blank, it is the first time

adjustment. If the table shows the previous value

setting, the current setting must be changed back

to the original default setting prior to making any

adjustment.

5) Make sure the adjusting plate is aligned with the

default marking line on the housing. If it is not

aligned, rotate the adjusting bolt with a wrench until

it is aligned. At this position the water regulating

valve is returned to the original default setting.

6) Rotate the adjusting bolt with a wrench to adjust

the valve temperature setting according to the

“Valve Setting Guide Table” on page 26. The

painted line on adjusting bolt and housing is for

rotational reference to complete one rotation

(360 °).

< NOTE >

The default marking line on the housing is for

adjustment reference. The painted line on

adjusting bolt and housing is for rotational

reference. Each completed rotation of the

adjusting bolt is resulting in about 0.04 inch (1

mm) displacement of the adjusting plate.

ILL00147-00

Screws (5)

ILL00148-00

Screws (7)

Screws (3)

Screws (3)

ILL00179-00

Lower

Higher

Painted line

Adjusting Bolt

ILL00185-00

Default Marking Line

Adjusting Plate

Direction of Rotation

Temperature Setting

Clockwise

Lower

Counterclockwise

Higher

Advertising