background image

Repair Section

41

Show LCD and LED

all on mode

Press HI/LO and

 buttons simultaneously for 3 seconds to check LCD

segments and LED display.

After 5 seconds, display goes back to normal operation mode.

Key lock mode (LCD

displays “LOCKED”.)

Press ENTER and SET CLOCK buttons simultaneously for 5 seconds to

lock all buttons on the controller panel (except keypad lock and unlock

operations).

To unlock, press and hold ENTER and SET CLOCK buttons

simultaneously for 5 seconds again.

Indication of model

name

Press UP and DOWN buttons simultaneously for 5 seconds to display a

model name.

After 5 seconds, display goes back to normal operation mode.

Detection of unit stop

signal from fire alarm

system

Signal is input from the fire alarm.

(Unit stops, output signal (J106) turns on and buzzer sounds.)

Indication of service

code

Press ON/OFF and

 buttons simultaneously for 3 seconds. Indication

contents is as follows.

To exit service code, press ON/OFF button.

Activation of high

pressure switch

When high pressure switch (connected to J104) is activated (=J104 input

turns to open) for the first 2 times in 24 hours, LCD indicates “HP” but

goes away as the high pressure switch resets. If the high pressure switch

is activated 3 times in 24 hours, LCD indicates blinking “HP” and signal

output (J106) turns on. When the high pressure switch is activated 10

times in 24 hours, LCD indicates “FAIL HP” and signal output (J106) turns

on, then buzzer sounds.

LCD Display

Description

Condition

START
STOP
CLOCK

MO TU WE TH FR

AM

F

C

F

C

PROGRAM

LOCKED

ON

PM

SA SU

SET TEMP

ROOM TEMP

HI

LO
ON
OFF

COOL

FAN

TU

AM

F

LOCKED

SET TEMP

HI

ON

COOL

FAN

LCD

DF

FZ

OD

Description

Value

Defrost status
Evap. out pipe

temperature

26⇔109F

(“26”⇔“X9”)

Outdoor

temperature

0 (“00”)

START

STOP

CLOCK

MO

TU

WE TH FR

AM

F
C

F

C

PROGRAM

LOCKED

ON

PM

SR SU

SET TEMP

ROOM TEMP

HI

LO

ON

OFF

COOL

FAN

START

STOP

CLOCK

MO TU WE TH FR

AM

F
C

F
C

PROGRAM

LOCKED

ON

PM

SR SU

SET TEMP

ROOM TEMP

HI

LO

ON

OFF

COOL

FAN

Advertising