Repair Section

66

11.2 Removal of Refrigeration and Water System Components

WARNING

• Before replacing any refrigeration and water system component, recover the refrigerant

using standard recovery procedures and drain the water from the unit.

• When recovering the refrigerant, use the pinch-off tubes at the low pressure side (tube 1)

and high pressure side (tube 2) as shown in the figure below.

CAUTION

• To prevent oxidation, dry nitrogen should be conducted (flow rate 0.27 gal/min (1 L/min)) through

the pinch-off tube during any brazing operation.

• During any component replacement involving brazing, shield nearby parts with a steel plate, etc.,

to protect them from the flame.

< NOTE >

When replacing the compressor, attach the pipe 1 and the pipe 2 packaged in the compressor

assembly.

ILL00157-00

High Pressure Switch

D

I, L, M

Water Regulating Valve

Compressor

A, H

B, C, J, K

E, F, G

E, H

Condenser
Capillary Tube
Evaporator

Part to Replace

Disconnect At

D

F

G

H

I

J

K

Tube 2

Tube 1

L

M

C

E

A

Pipe 2

Pipe 1

B