44 (2) unit does not operate – MovinCool Office Pro W20 Service Manual User Manual

Page 44

Advertising
background image

Repair Section

44

(2) Unit does not operate

< NOTE >

• In this case, there is a possibility of safety device activating due to the clogged air filter. So make

sure to first clean the air filter and then start up again to confirm if the problem lies with the air filter.

• Check the installation site for operating temperature and installation space (unobstructed airflow).

• If cooling water is not supplied to the unit, a safety device is activated. Check the water flow to

confirm if the problem lies with the water flow.

Condition

Check Area

Possible Cause

Remedy

Unit does not operate.

Unit does

not operate.

Control

Panel

display

turns off.

1. Voltage.

Power failure.

Repair power.

2. Ground fault breaker trip.

Ground fault or defective

ground fault breaker.

Repair ground fault section.

Reset or repair breaker.

3. LCDI power cord trip.

Leakage current detected.

Reset power cord.

Replace power cord.

4. Fuse.

Fuse blown.

Repair shorting section.

Replace fuse on the relay

board.

Control

panel

display

turns on

Control

Panel

display

shows error

codes.

1. Display code “FL”.

Drain tank (optional) is filled

with the drain water.

Discharge the drain water.

RESET the controller

*1

.

Loose drain switch

connection.

Reconnect the drain switch

and check the connection.

RESET the controller

*1

.

Defective drain switch.

Replace drain switch.

RESET the controller

*1

.

2. Display code “AS”.

Optional condensate pump

stops pumping water due to

any kinks and/or blockage in

the drain line or due to

improper routing of the drain

line.

Remove any blockage or

kinks from the drain line or

improve hose installation.

RESET the controller

*1

.

Defective condensate pump. Replace the condensate

pump.

RESET the controller

*1

.

Missing jumper connector.

Insert the jumper connector

and check the connection.

RESET the controller

*1

.

*1 : To RESET the controller, press ON/OFF and HI/LO buttons simultaneously for 5 seconds.

Advertising