26

7) Write the value setting with a permanent marker

on the adjustment record table on the inside

panel of the unit.

< NOTE >

Recording the value setting is very important

for reference when making future adjustments.

Valve Setting Guide Table

Adjustment Record (Example)

CAUTION

Do not forget to write down the value setting with a permanent marker on the adjustment record

table. This is the only way to know the current valve setting. It is difficult to exactly adjust the

valve without the current valve setting. Failure to adjust the valve may damage the unit and void

the warranty.

Setting

Direction of Valve Rotation Number of Rotation Valve Opening Temperature

Minimum Water Temperature

A

Clockwise

4

72 °F (22 °C)

40 °F (4.4 °C)

B

3

75 °F (24 °C)

47 °F (8 °C)

C

2

79 °F (26 °C)

54 °F (12 °C)

D

1

82 °F (28 °C)

61 °F (16 °C)

E

Default Setting Point

-

86 °F (30 °C)

68 °F (20 °C)

F

Counterclockwise

1

90 °F (32 °C)

72 °F (22 °C)

G

2

94 °F (34 °C)

75 °F (24 °C)

H

3

96 °F (36 °C)

79 °F (26 °C)

I

4

100 °F (38 °C)

83 °F (28 °C)

No.

Setting Date

Setting

No.

Setting Date

Setting

0

-

E

11

Dec. 10, 2010

B

Apr. 10, 2011

D

Aug. 10, 2011

G

10

21

Advertising