9.2 Self-Diagnostic Codes

• Self-diagnostic codes are displayed on the control board under the following conditions. Refer

to the troubleshooting chart on page 44 to 46 for the remedies.

LCD Display

Description

Condition

Drain tank is full

When the drain tank is filled with drain water.

(“TANK FL” LED flashes and signal output (J106) turns on.)

Condensate pump

problem

When the (optional) condensate pump stops pumping water due to any

kink and/or blockage in the drain line or due to improper routing of the

drain line, the compressor shuts off, and LCD indicates “AS”.

(J8 input of relay board turns to open and signal output (J106) turns on.)

Defect (short or open)

of room thermistor

When room thermistor (connecting to J101) becomes short or open.

(Signal output (J106) turns on.)

Defect (short or open)

of freeze protection

thermistor

When freeze protection thermistor (connecting to J102) becomes short or

open. (Signal output (J106) turns on.)

Show running hours

of compressor

Press ON/OFF and

buttons simultaneously for 3 seconds, total

operation hours of compressor is indicated by 6-digit (hours).

Example in left: 807 hours

After 5 seconds, display goes back to normal operation mode.