9.5 Inspection of Capacitor (for Fan Motor and Compressor)

(1) Ohmmeter method

• Set the ohm-meter to the 10M range. Place the

two probes against the two terminals of the

capacitor. At first, the ohm-meter should

indicate small value, then the reading should

gradually increase towards infinity. This

indicates that the capacitor is charging. If the

reading indicates infinity right away (open) or

the ohm-meter fails to move from 0. (shorted),

replace the capacitor.

(2) Capacitance tester method

• Using a capacitance tester and the chart on page 29, test the capacitor for the value indicated.

If the value tested is not within 10 % of indicated capacitance, replace the capacitor.

WARNING

• Properly discharge the capacitor(s) before testing and after testing has been completed.

• Failure to do so could cause damage to test equipment or the unit and/or result in

personal injury (electrical shock) or death.

9.6 Inspection of Drain Switch

• Check for continuity between terminals 1 and 2

when drain switch is pressed. With drain switch

depressed, there is no continuity between

terminals 1 and 2. Replace drain switch if

continuity does not satisfy the above condition.

I001808

I001809

2

NC

C

1

DS2

DS1

To J103

Drain Switch

Top of Base Plate