Engineering labels for optical fibers

These labels are affixed to optical fibers that connect the fiber ports on the cards in a chassis, or connect

fiber ports on box-type devices. The following two types of labels are used for optical fibers:

Labels for a fiber that connects the fiber ports on two devices

Table 86 Information on labels affixed to the fiber between two devices

Content Meaning

Example

MN-B-C-D-R/T

MN—Rack number

M—Row number of the rack in the

equipment room, in the range of A to Z.

N—Column number of the rack in the

equipment room, in the range of 01 to 99.

For example, A01.

B—Chassis number

Numbered in top-down order with two digits,
for example, 01

C—Slot number

Numbered in top-down and left-right order
with two digits, for example, 01.

D—Fiber port number

Numbered in top-down and left-right order
with two digits, for example, 05.

R—Optical receiving interface
T—Optical transmitting interface

N/A

MN-B-C-D-R/T

MN—Rack number

The meanings are the same as above. If the
local device and the peer device are not in the

same equipment room, MN can be the name

of the equipment room.

B—Chassis number

C—Slot number

D—Fiber port number

R—Optical receiving interface
T—Optical transmitting interface

N/A

Figure 90 Example of a label on an optical fiber between two devices

{

A01-01-05-05-R—The local end of the optical fiber is connected to Optical Receiving Interface
05 on Slot 5, Chassis 01 in the rack on Row A, Column 01 in the equipment room.

{

G01-01-01-01-T—The peer end of the optical fiber is connected to Optical Transmitting Interface
01 on Slot 01, Chassis 01 in the rack on Row G, Column 01 in the equipment room

Labels for a fiber that connects the device and the optical distribution frame (ODF)