75

Figure 54 Securely fasten cables

(1) Flat washer

(2) Spring washer

(3) Nut

Fasten heavy or rigid power cables at the connectors to relief stress.

Do not use tapping screws to fasten the connecting terminals.

Bind together cables that are the same type and routed in the same direction.

Table 40

lists the cable bundling specifications.

Table 40 Cable bundling specifications

Cable bundle diameter (mm)

Space between bundles (mm)

10

80 to 150

10 to 30

150 to 200

30 200

to

300

Do not tie cables or bundles in a knot.

The metal parts of the crimped cold-pressed terminal blocks (such as circuit breaker) cannot
protrude beyond the blocks.

(1) (1)(2)

(3)

(1) (1)(2)

(3)