The heat value shown in the cooling capacity column represents the allowable heat value

when air temperature rise inside the cabinet is less than 10”C.

(Example) Allowable Heat Value inside Cabinet with Heat Exchanger

The heat value inside the cabinet required to keep the inner-air temperature rise below

with the Heat Exchanger HEATEX 02 installed inside the cabinet as in the example (1) is:

P = k A

=6 X3 X1 O+25O

Accordingly, the heat value should

(3) Installation of

Heat Exchanger

be less than 430w.

UPPER

A heat exchanger is installed to the cabinet made

CABINET

by a machine tool maker.

Shown above is an example of heat exchanger

installation.

Install the heat exchanger so that the

inner air is taken in from the upper section and

OUTER-AIR
FLOW

discharged from the lower section while the

\

LOWER

side air is taken in from the lower section and

H EAT

EXCHANGER

charged from the upper section. (For details re-
garding installation, see Appendix 16. Dimensions

Fig.

of heater exchanger. )

4.3 HEAT VALUES

OF UNITS

(1) NC UNIT

Unit

Heat Value (W)

CPU Module

70

to

160

9“ CRT Operator’s Panel

20

T a p e R e a d e r

I

25

NOTE :

The heat value of the CPU module varies with option addition

Advertising