2 power line protection – Yaskawa i80M Connecting Manual User Manual

Page 319

Advertising
background image

2 POWER LINE PROTECTION

The Servopack is operated through the commercial power line (200 V). To prevent the power

line accidents due to grounding error, contact error, or to protect the system from a fire, circuit
breakers

or fuses must be installed according to the number of Servopack used (Table

2).

A quick-melting fuse cannot be used, because the Servopack used the capacitor-input

power supply and the charging current might melt such a fuse.

Table A7. 2 Power Supply Capacity and MCCB or Fuse Capacity

Servopack

Power Capacity*

Current Capacity per

Type

per Servopack

MCCB or Fuse

kVA

A

1.1

5

IR1OSB

2.1

8

3.1

10

4.1

12

6.0

18

IR44SB

8.0

24

Values at rated load

319