Riello UPS PowerShield³ User Manual

Page 21

Advertising
background image

UPSMON User Manual

Advanced UPSMON Configuration

21

System shutdown

This field is used to specify the parameters for the system shutdown, the system Shutdown can
be triggered by either a specified time after AC Fail or if the UPS autonomy time is below a
specified time. If the UPS sends a low battery signal to the computer (i.e. the UPS backup time is
low), the Upsagent will ignore the specified times and start the system shutdown procedure
immediately.

UPS shutdown

This field can be used to send a shutdown signal to the UPS once all remote computers have
shutdown, at this point the UPS will then shutdown

1.3.2

Parallel group configuration (select the Configure button)

Parameter name

Parameter description

Enable parallel function

Enable or disable the parallel functionality.

Disable actions on single Ups

If selected, the standard configuration for the single UPS event will be ignored. The Upsagent
controls only the group status. If it is not selected, the Upsagent controls both the group events
and also the single UPS events. If this parameter is selected, the job actions defined in the job
dialog box are disabled for the single UPS.

Consider a Ups with lost
communication as an alarm

If selected, the active alarm level is raised, specified on the parallel event list, for each UPS in
communication lost condition.

Disable the System shutdown from
a single UPS

If selected, this disables the system and UPS shutdown time defined on the single UPS
configuration. This function shutdown time is the same time for the UPS parallel group.

Advertising