Reference Manual

00809-0100-4530, Rev BA

July 2009

Rosemount 5300 Series

5-34

Submerged is used for applications where the probe is fully submerged in
liquid. In this mode, the transmitter ignores the upper product level. See
Section 7: Interface Measurements with Fully Submerged Probes” for more
information.

NOTE!
Only use Submerged for applications where the interface is measured with a
fully submerged probe.

F

OUNDATION

Fieldbus parameter:

TRANSDUCER 1100>MEAS_MODE

Dielectric Constant/Dielectric Range

The dielectric constant of the product is used for setting the appropriate signal
amplitude thresholds, see Section 7: Service and Troubleshooting for more
information on amplitude threshold settings. Normally, this parameter does
not need to be changed for level measurements. However, for some products,
measurement performance can be optimized by setting the proper product
dielectric constant.

For Interface Level measurements, the dielectric constant of the upper
product is essential for calculating interface level and the upper product
thickness. By default, the Upper Product Dielectric parameter is about 2.

Set the Upper Product Dielectric Constant to a value that corresponds to
the current product.

F

OUNDATION

Fieldbus parameters:

TRANSDUCER 1100>PRODUCT_DIELEC_RANGE
TRANSDUCER 1100>UPPER_PRODUCT_DC

Process Conditions

Select the Rapid Level Changes check-box only if the surface is moving
quickly up or down at rates over 1.5 in./s (40 mm/s).

F

OUNDATION

Fieldbus parameter:

TRANSDUCER 1100>ENV_ENVIRONMENT

14. To configure volume calculation, select the TRANSDUCER1300 block and

choose the Volume tab.