Rosemount 5300 series, Reference manual, Remote housing measuring range – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 192

Advertising
background image

Reference Manual

00809-0100-4530, Rev BA

July 2009

Rosemount 5300 Series

A-8

Remote Housing
Measuring Range

This table shows the maximum recommended measuring range with Remote
Housing for different RH lengths, installation types, Dielectric Constants, and
probe types.

Table A-2. Remote Housing
measuring range

Dielectric

Constant

Rigid Single

8 mm

Rigid Single

13 mm

Flexible Single

Coaxial

Rigid Twin

Flexible Twin

1 m
Remote
Housing

Chamber / pipe
installations

≤ 4 in.

(100 mm)

1.4

2

80

1.4

2

80

4 ft (1.25 m)
10 ft (3 m)

(1)

10 ft (3 m)
4 ft (1.25 m)
4 ft (1.25 m)
10 ft (3 m)

(1)

15 ft (4.5 m)

(1)

15 ft (4.5 m)

(1)

15 ft (4.5 m)

(1)

4 ft (1.25 m)
4 ft (1.25 m)
10 ft (3 m)

(1)

33 ft (10 m)

(1)

(2)

33 ft (10 m)

(1)

(2)

33 ft (10 m)

(1)

(2)

4 ft (1.25 m)
4 ft (1.25 m)
159 ft (48.5 m)

(1)

19 ft
(6 m)

10 ft (3 m)

(1)

10 ft (3 m)

(1)

10 ft (3 m)

(1)

4 ft (1.25 m)
4 ft (1.25 m)
10 ft (3 m)

(1)

33 ft (10 m)

(1)

(2)

33 ft (10 m)

(1)

(2)

33 ft (10 m)

(1)

(2)

4 ft (1.25 m)
98 ft (30 m)

(1)

159 ft (48.5 m)

(1)

Tank installations

2 m
Remote
Housing

Chamber / pipe
installations

≤ 4 in.

(100 mm)

1.4

2

80

1.4

2

80

9 ft (2.75 m)
10 ft (3 m)

(1)

10 ft (3 m)
9 ft (2.75 m)
9 ft (2.75 m)
10 ft (3 m)

(1)

15 ft (4.5 m)

(1)

15 ft (4.5 m)

(1)

15 ft (4.5 m)
9 ft (2.75 m)
9 ft (2.75 m)
10 ft (3 m)

(1)

33 ft (10 m)

(1)

(2)

33 ft (10 m)

(1)

(2)

33 ft (10 m)

(1)

(2)

9 ft (2.75 m)
9 ft (2.75 m)
154 ft (47 m)

(1)

19 ft
(6 m)

10 ft (3 m)

(1)

10 ft (3 m)

(1)

10 ft (3 m)

(1)

9 ft (2.75 m)
9 ft (2.75 m)
10 ft (3 m)

(1)

33 ft (10 m)

(1)

(2)

33 ft (10 m)

(1)

(2)

33 ft (10 m)

(1)

(2)

9 ft (2.75 m)
98 ft (30 m)

(1)

154 ft (47 m)

(1)

Tank installations

3 m
Remote
Housing

Chamber / pipe
installations

≤ 4 in.

(100 mm)

1.4

2

80

1.4

2

80

10 ft (3 m)

15 ft (4.5 m)
15 ft (4.5 m)
15 ft (4.5 m)
14 ft (4.25 m)
14 ft (4.25 m)
15 ft (4.5 m)

(1)

33 ft (10 m)

(1)

(2)

33 ft (10 m)

(1)

(2)

33 ft (10 m)

(1)

(2)

14 ft (4.25 m)
14 ft (4.25 m)
149 ft (45.5 m)

(1)

19 ft
(6 m)

10 ft (3 m)

(1)

33 ft (10 m)

(1)

(2)

33 ft (10 m)

(1)

(2)

33 ft (10 m)

(1)

(2)

14 ft (4.25 m)
98 ft (30 m)

(1)

149 ft (45.5 m)

(1)

Tank installations

(1) Accuracy may be affected up to + 1.2 in. (30 mm).
(2) Required chamber/pipe size is 3 or 4 in. (75 -100 mm).

Advertising